Boiler Controller For Ship Application:
Application Example: Mitsubishi MAC boiler
MAC-20B MAC-25B MAC-30B MAC-35B MAC-40B MAC-45B MAC-50B
MAC-55B MAC-60B MAC-70B MAC-80B MAC-90B MAC-100B MAC-110B
Model No.: KMM901
Maker: Yamatake- Honeywell
Control Input/Output Signals J21
|
Panel Input/Out Put Signals J22
|
|
A
|
IN5+
|
1~5V voltage input +
|
A
|
+24V
|
+ 24V voltage output +
|
B
|
IN5-
|
1~5V voltage input -
|
B
|
+24V
|
+ 24V voltage output +
|
C
|
IN4-
|
1~5V voltage input -
|
C
|
+24V
|
+ 24V voltage output +
|
D
|
IN4+
|
1~5V voltage input +
|
D
|
+24V
|
+ 24V voltage output +
|
E
|
OUTV2-
|
1-5V voltage output -
|
E
|
AUTO.O
|
Auto mode Signal output
|
F
|
OUTV1+
|
1-5V voltage output +
|
F
|
MAN.O
|
Man mode signal output
|
H
|
OUTV1-
|
1-5V voltage output -
|
H
|
---
|
---
|
J
|
IN3-
|
1~5V voltage input -
|
J
|
---
|
---
|
K
|
IN3+
|
1~5V voltage input +
|
K
|
---
|
---
|
L
|
OUTV2+
|
1-5V voltage output +
|
L
|
CAS.O
|
CAS mode signal output
|
|
|
|
|
|
|
|
|
|
|
|
4-20mA out put for VP meter -
|
|
|
|
|
|
|
4-20mA out put for VP meter +
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Main power supply for instrument
|
|
|
|
4-20mA out put for PV meter -
|
|
|
|
Main power supply for instrument
|
|
|
|
4-20mA out put for SP meter -
|
|
|
|
|
|
|
|
|
|
|
|
|
4-20mA out put for SP meter +
|
|
|
|
|
|
|
|
|
|
|
|
|
4-20mA out put for PV meter +
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply for standby manual +
|
|
|
|
|
|
|
Power supply for standby manual +
|
|
|
|
|
|
|
External Interlock signal
|
|
|
|
Interlock mode signal output
|
|
|
|
|
|
|
|
|
|
|
|
|
Display change signal input
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MAN output lowering signal input
|
|
|
|
|
|
|
|
|
|
|
|
|
Interlock reset signal input
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
About MADIC abnormal:
When the KMM901 controller becomes abnormal, a signal named CPU FAIL and INTERLOCK will be issued. These signal will turn on this light of Master controller abnormal or Airflow controller abnormal or Feed water
controller abnormal. At the menatime, it will send the same signals to sequencer controller for alarming
Component of this controller:
KMM P.C.B. - BUF II Board Assy. for KMM P/N. 80341018-001 (SDD-006-1)
KMM P.C.B. - Mother Board Assy. for KMM P/N. 80341167-001
KMM P.C.B. - CPU Board for KMM P/N. 80341069-001
KMM P.C.B. - IOC Board for KMM P/N. 80341015-001
KMM P.C.B. - DC / DC Converter P/N. 80350851-001
KMM P.C.B. - Data Setting Unit P/N. 82407941-001
Experienced problem for this type controller:
Data setting unit insert cause boiler abnormal;
When ship moved from hot area (Dubai) to cold area (winter in China), all the KMM901 controller become abnormal;
Controller suddenly stop working, but after power off it works again;
The indication of SP, PV and VP has too much error even when all the meters are accurate;
In twin boiler system, the indications of the SP meter are different